Tube bundle header
type
|
|
A tube
bundle is an assembly of tubes, headers, side frames, and tube supports as
shown in figure below. Usually the tube surface exposed to the passage of air
has extended surface in the form of fins to compensate for the low heat
transfer rate of air at atmospheric pressure and at a low enough velocity for
reasonable fan power consumption.
The box
header consists of tube sheet, top, bottom, and end plates, and a cover plate
that may be welded or bolted on. If the cover is welded on, holes must be
drilled and threaded opposite each tube for maintenance of the tubes. A plug is
screwed into each hole, and the cover is called the plug sheet. Bolted
removable cover plates are used for improved access to headers in severe
fouling services. Partitions are welded in the headers to establish the
tube-side flow pattern, which generates suitable velocities in as near
countercurrent flow as possible for maximum mean temperature difference. Partitions
and stiffeners (partitions with flow openings) also act as structural stays.
Horizontally split headers may be required to accommodate differential tube
expansion in services having high fluid temperature differences per pass. The
figure below illustrates common head types.
|
|

|
Plug
type This
is the best suited for a high pressure application up to 3,300 psig
(230kg/cm2G). the individual tube is accessible for cleaning and tube plugging
|
|

|
(Removable)
Cover plate type This
is best suited for the fluid of hghly foulding tendency because of easy access
to all tubes. This is applicable for a
moderately high pressure up to 500 psig (35kg/cm2G)
|
|

|
Bonnet
type This
type is suited for a high-vaccum operation. The bonnet type eliminates welding
joints of the box type.
|
|

|
Manifold
type This
type is a vacuum steam condensers of a power plant application. The large
manifold ensures the low pressure drop so that the flow rates become equal to
every tube.
|
|
 Cooling
Water Module for GE Power System |
|
This special
'Cooling Water Module' is a system for the water cooling and pumping
unit for the circulating cooling water system of a GE Frame gas
turbine w/H2 cooled Generator. All components of the Cooling Water
Module have been mounted, piped and wired in our factory. The Design
Standards has been incorporated with ASME, AWS, ASTM, AISC, NEMA,
OSHA, ICBO, TEMA, SSPC, NFPA. |
|
|
|

|
|
|